The “Dual Nature” of Dielectric Esters: When Extreme Cold Challenges Safety Expectations

Over the last two decades, the power transformer industry has undergone a quiet but profound revolution. The urgent need to reduce environmental impact and enhance fire safety has driven the transition from traditional mineral oils to alternative fluids, specifically natural and synthetic esters.

The advantages are well-documented in literature and standards such as CIGRE Brochure 436: a high fire point (>300°C, K-class), excellent biodegradability, and a superior moisture management capability that has fundamentally redefined our calculations for the service life of solid insulation.

However, in electrical engineering, a golden rule applies: every exceptional property carries a “flip side.” For esters, this “blind spot” emerges when we step outside the ideal thermal regime and confront the challenges of harsh climates and extreme low temperatures. In 35 years of laboratory experience, I have observed that while mineral oil behaves in a “predictable” manner—due to its known limitations—esters create an expectation of invulnerability that must be scientifically qualified to ensure grid reliability.

To understand why an ester behaves differently than mineral oil, we must look at its molecular structure.

Mineral oil, being non-polar, has a very low affinity for water. As established by Du et al. (1999), moisture in mineral oil-filled transformers resides almost entirely in the paper insulation or exists as free water once the very low saturation limit is reached.

Esters, conversely, possess polar functional groups (oxygen-rich carbonyl groups).


These sites allow for the formation of hydrogen bonds with water molecules, enabling the fluid to “host” a significantly larger amount of moisture. At 60°C, a synthetic ester can manage over 2500 ppm of water, acting as a dynamic buffer that extracts moisture from the kraft paper. This mechanism slows down the depolymerization of the cellulose by reducing the water available for the hydrolytic degradation of the paper, leading to the widely held belief in the “invulnerability” of ester filled systems.

The problem arises because this bonding capacity is not a static property, but a thermodynamic equilibrium highly sensitive to temperature. As the temperature drops, the molecular kinetic energy decreases, and the hydrogen bonds become less effective at stabilizing the water molecules within the fluid matrix.


Temperature (°C)Mineral Oil (ppm)Natural Ester (ppm)Synthetic Ester (ppm)
+60 °C (Operating)≈200≈1600≈2500
+20 °C (Ambient)≈45≈550≈1100
0°C (Freezing)≈20≈220≈450
–20 °C (Extreme Cold)≈8≈60≈120
Table 1: Saturation Limits (ppm) and Precipitation Risk


According to the solubility curves (see Martin et al., 2012), the water holding capacity of a synthetic ester drops by nearly an order of magnitude between +20°C and −20°C. If a fluid is maintained at 400 ppm (often considered “dry” for esters at operating temperatures), it will inevitably reach a state of over-saturation as the temperature falls, leading to phase separation.

The “dual nature” of esters is a direct result of three fundamental technical trade-offs:

1. The Polarity Paradox
The very polarity that protects the paper at 60°C is what causes sharp precipitation at −20°C. Unlike mineral oil, which is consistently “poor” at holding water, esters provide a false sense of security. At operating temperatures, water is “locked” in the fluid. At −20°C, the fluid “unlocks” this moisture, forcing it out of solution.

2. Fire Safety vs. Viscosity
Esters consist of heavy, complex molecules (triacylglycerols in natural esters or pentaerythritol esters in synthetics). While this ensures a high fire point, it results in a much higher viscosity at low temperatures. In extreme cold, the kinematic viscosity of an ester can reach 2000−3000 mm2/s, effectively stalling natural oil flow. This creates “cold dead zones” where moisture precipitates long before the bulk oil sensors register a temperature drop.

3. Biodegradability vs. Hydrolysis
The ester bonds are susceptible to hydrolysis. If an ester is allowed to operate with high water content, it can produce fatty acids. While these acids are long-chain and less aggressive to paper than the short-chain acids found in mineral oil, they increase the fluid’s acidity and can influence its dielectric dissipation factor (tanδ), further complicating the stability of the fluid during thermal cycling.

One of the most critical, yet under studied, aspects of this phenomenon is the kinetics of moisture migration. When a transformer cools down—for example, during an unplanned outage in winter—the fluid’s saturation limit drops rapidly. However, the paper insulation is a porous medium with a high affinity for water. Experimental data indicates that as the fluid becomes over-saturated, the excess water molecules do not simply stay in the oil. They migrate toward the nearest solid surface. Because the paper is already polar and contains hydroxyl groups, it acts as a “magnet.” During a rapid cooldown, the water moves faster than the fluid can circulate. This leads to a localized concentration of moisture at the oil-paper interface. The result is a “wetting” of the paper surface even if the core of the paper insulation remains relatively dry. This surface saturation is a primary driver for tracking and flashover.

Managing esters requires a shift in laboratory diagnostics. Traditional Karl Fischer titration (IEC 60814) provides the total amount of water in ppm, but in the context of extreme cold, ppm is a misleading metric.

A fluid with 100 ppm of water is perfectly safe at 20°C (10-20% saturation). But the same 100 ppm at −25°C means the fluid is at 150% saturation, implying that free water must exist. In my laboratory, we emphasize the use of Water Activity (Ws) sensors. Water activity measures the “relative saturation” of the fluid. An aw of 0.5 means the oil is at 50 % of its capacity, regardless of the temperature. For esters in cold climates, monitoring Ws is the only way to predict when the “Dual Nature” will trigger a phase separation.

Furthermore, Dissolved Gas Analysis (DGA) interpretation must be adjusted. The stray gassing behavior of esters—particularly the production of ethane (C2H6) and hydrogen (H2) at lower temperatures compared to mineral oil—can lead to false positives if the laboratory does not use ester-specific Duval Triangles or Rogers’ Ratios.


In my 35 years of experience, I have found that visual evidence is the best teacher. By pushing a saturated ester system to −24°C in a controlled environment, we can simulate a “Cold Start” scenario:

  1. The “Fog” Effect: The fluid undergoes a visible phase separation. Micro-droplets of water precipitate, creating a dense “fog.” Under the influence of an electric field, these droplets polarize and elongate, creating “streamers” that lower the inception voltage of partial discharges.
  2. Surface Nucleation (Frosting): The kraft paper becomes coated in a white, crystalline patina. This is not ambient frost; it is moisture being “vomited” by the ester directly onto the solid insulation.
  3. The Dielectric Trap: If the transformer is energized in this state, the dielectric strength of the liquid-solid interface is at its absolute minimum. As the transformer begins to heat up, it takes hours for the viscous ester to circulate and re-absorb this moisture. This “danger window” is where most cold-climate failures occur.

To ensure safety, we must move beyond the “install and forget” mentality. Based on IEEE C57.147 and IEC 60422 principles, I recommend:

  • Enhanced Dehydration: For transformers destined for cold climates, esters must be processed to ultra-dry levels (<10 relative saturation at 20°C) before commissioning.
  • Smart Breathers: The use of maintenance-free dehydrating breathers is mandatory to prevent the ester from using its hygroscopic nature to “pull” moisture from the atmosphere.
  • Thermal Pre-heating: In extreme cases, internal heaters or specific “warm-up” protocols should be used to bring the fluid temperature above 0°C before applying full load.


Dielectric esters are an extraordinary tool for modern grid resilience and sustainability. However, their “dual nature” demands a higher level of technical culture. We cannot treat them as “environmentally friendly mineral oil.” They are complex chemical systems that require precise moisture management. Understanding the thermodynamic limits of these fluids is the only way to transform the pursuit of environmental safety into a guarantee of operational reliability. By making the invisible visible—whether through aw sensors or −24°C laboratory simulations—we empower asset managers to protect their investments against the hidden risks of the cold.

References:

[1] IEC 60422, Mineral insulating oils in electrical equipment – Supervision and maintenance guidance.
[2] CIGRE Brochure 436, Experiences in service with new insulating liquids (2010).
[3] Du, Y., Zahn, M., et al. (1999), “Moisture equilibrium in transformer insulation systems”, IEEE Electrical Insulation Magazine.
[4] Martin, D., et al. (2012), “Moisture solubility of natural ester and mineral oil mixtures”, IEEE Transactions on Dielectrics and Electrical Insulation.
[5] IEEE C57.147, Guide for Acceptance and Maintenance of Natural Ester Fluids in Transformers.
[6] Fofana, I., et al. (2011), “Comparative studies of the physico-chemical properties of mineral oil and ester fluids”, IEEE Transactions on Dielectrics and Electrical Insulation.


Pierluigi De Horatiis is the director of an ISO/IEC 17025 Accredited Laboratory with over 35 years of experience in the analysis and treatment of insulating fluids. He is an expert member of Technical Committee 10 (Insulating Fluids) of the CEI/IEC. A passion ate advocate for chemical experimentation and technical dissemination, he works to bridge the gap between laboratory research and field safety, making the complex phenomena inside power transformers visible to the engineering community.

This article was originally published in the September 2026 issue of the Innovations In Insulation Systems magazine.